FUSETEK JLS-200 Powr-Gard® Cartridge Fuse Fast-Acting, Current-Limiting Class J 200 A, 600 VAC
Description
JLS series fuses provide space-saving, fast-acting overload and short-circuit protection for non-inductive loads. When used for motors or other inductive loads, the ampere rating of JLS series fuses must be increased to prevent nuisance opening on inrush currents. In such applications, JLS fuses may provide only short circuit protection. Consider using Littelfuse POWR-PRO™ JTD series time-delay fuses in such circuits. General purpose circuits with little or no motor load. Resistive loads, such as resistance electric heat. Loads requiring fast-acting overload protection, such as equipment containing solid-state devices.
Specifications
Brand Name | Littelfuse | Sub Brand | Powr-Gard® |
Item Name | Cartridge Fuse | Type | Fast-Acting, Current-Limiting |
Series | JLS | Voltage Rating | 600 VAC |
Amperage Rating | 200 A | Interrupt Rating | 200 kA |
Fuse Class | Class J | Mounting Type | Bolt-On |
Terminal Connection | Knife Blade | Element Type | Single |
Indication | Non-Indicating | Construction | Melamine |
Dimensions | 1-1/2 in dia x 5-3/4 in L | Standards | UL File Number E81895, CSA File Number LR29862, Federal Specification WF-1814, CE Certified |
Application | Power Conversion Device Protection, Variable Speed Drives, Rectifiers, Resistive Loads, Solid-state Devices |
Packages
1 - rarr_unit_1 |